Logo Bihl+Wiedemann GmbH

Safety I/O Modules

Bihl+Wiedemann offers the right module for accessing any safety input signal. Both control cabinet modules (IP20) and field modules (IP67) are available. From a single safety input or output to safety multi-I/O modules we offer the right ASi modul for your requirements. Many of our modules also include available outputs for standard signals.

 

Safety I/O Modules: Input/output modules, IP20

  • All Safety I/O Modules: SIL 3, Cat. 4, PLe
  • Compact form factor
  • Safety inputs
  • Safety outputs
  • Additional standard inputs and standard outputs
Figure Inputs Safety, SIL 3, Cat. 4 Safety signal inputs Outputs Safety, SIL 3, cat. 4

inputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

Input voltage (sensor supply)

Electronic outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

Output voltage (actuator supply)
Length of connector cable

AB address (max. 62 AB addresses/ASi network), 2 AB addresses (max. 31 modules with 2 AB addresses), Single addresses (max. 31 Single addresses/ASi network), ASi-5 address (max. 62 ASi-5 addresses/ASi network), mixed use allowed.
For ASi modules with two ASi nodes the second Asi node is turned off as long as the first Asi node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

ASi address
Article No.
BWU34288 x 2 channelsfloating contacts, optoelectronic protective devices, complementary switch1 release circuit, 1 x electronic safe outputs, augmented reliabilityout of AUXout of AUXunlimiteddepending on configuration, optimised for ASIMON360
BWU38836 x 2 channelsfloating contacts, optoelectronic protective devices, complementary switch2 release circuits, 2 x electronic safe outputs, augmented reliabilityout of AUXout of AUXunlimiteddepending on configuration, optimised for ASIMON360
BWU34274 x 2 channelsfloating contacts, optoelectronic protective devices, complementary switch2 release circuits, 2 x electronic safe outputs, augmented reliabilityout of AUXout of AUXunlimiteddepending on configuration, optimised for ASIMON360
BWU22361 x 2 channelsfloating contacts1 release circuit, 2 x relayout of AUX-unlimited2 Single addresses + 1 AB address
BWU36712 x 2 channelsfloating contacts, complementary optoelectronic protective devices-out of AUX-unlimited2 Single addresses
BWU36962 x 2 channelsfloating contacts, optoelectronic protective devices-out of AUX-unlimited2 Single addresses
BWU27072 x 2 channelsfloating contacts-out of AUXout of AUXunlimited2 Single addresses
BWU30131 x 2 channelsfloating contacts-out of AUXout of AUXunlimited1 Single address
BWU19391 x 2 channelsfloating contacts-out of ASiout of AUXmax. 15 m1 Single address
BWU27241 x 2 channelsfloating contacts-out of ASiout of ASimax. 15 m1 Single address
BWU25771 x 2 channelsoptoelectronic protective devices-out of AUXout of AUXunlimited1 Single address
BWU38821 x 2 channelscomplementary switch-out of ASiout of ASimax. 15 m1 Single address
BWU26611 x 2 channels; SIL 2, Cat. 3safety mats 1.2 kΩ or 8.2 kΩ monitoring resistor-out of AUXout of AUXmax. 15 m1 Single address
BWU26921 x 2 channels4 ... 20 mA / 0 ... 10 V / Pt100-out of AUX-unlimiteddepending on configuration
BWU32711 x 2 channelsthermocouples-out of ASi-unlimiteddepending on configuration
BWU2836--1-8 release circuits, 8 x electronic safe outputsout of AUXout of AUXunlimiteddepending on configuration
BWU3398--1 release circuit, 2 x electronic safe outputs, max. 3 A, augmented reliabilityout of AUXout of AUXunlimited1 Single address + 2 AB addresses
BWU2173--1 release circuit, 2 x electronic safe outputsout of AUXout of AUXunlimited1 Single address + 2 AB addresses
BWU3869--1 release circuit, 2 x electronic safe outputs, max. 3 A, augmented reliabilityout of AUXout of AUXunlimited1 Single address + 1 AB address
BWU2045--1 release circuit, 2 x relayout of ASi-I: max. 15 m; O: unlimited1 Single address + 1 AB address
BW3016--1 contact expander, 1 x electronic safe output 20 A-out of AUXunlimited-
BW3281--1 contact expander, 1 x electronic safe output 10 A-out of AUXunlimited-

 

 

Safety I/O Modules: Input/output modules, IP67, M12

  • Safety inputs SIL 3 Cat.4 and standard outputs in one module
  • Bicolor LEDs per output, state (yellow), overload (red)
Figure Inputs Safety, SIL 3, Cat. 4 Safety signal inputs Outputs Safety, SIL 3, cat. 4

inputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

Input voltage (sensor supply)

Electronic outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

Output voltage (actuator supply)
Length of connector cable

The connection to ASi as well to AUX (auxiliary 24 V power) is made via yellow resp. black ASi profile cable with piercing technology or via M12 socket (in IP20 via clamps).


Line protection: If the module is supplied via a M12 connection with A or B coding, it may only be used with a current load of max. 4 A per pin in acc. with IEC 61076-2-101 and IEC 61076-2-109. A fused tap is recommended. There is no such limitation for modules supplied via piercing contacts.

ASi connection

AB address (max. 62 AB addresses/ASi network), 2 AB addresses (max. 31 modules with 2 AB addresses), Single addresses (max. 31 Single addresses/ASi network), ASi-5 address (max. 62 ASi-5 addresses/ASi network), mixed use allowed.
For ASi modules with two ASi nodes the second Asi node is turned off as long as the first Asi node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

ASi address
Special function Article No.
BWU26312 x 2 channelsfloating contacts-out of ASi-max. 15 mASi profile cable2 Single addresses-
BWU22841 x 2 channelsfloating contacts-out of ASiout of AUXmax. 15 mASi profile cable1 Single address-
BWU23691 x 2 channelsfloating contacts-out of ASiout of AUXmax. 15 mASi via M121 Single address-
BWU22701 x 2 channelsoptoelectronic protective devices-out of AUXout of AUXunlimitedASi profile cable1 Single address-
BWU26891 x 2 channelsoptoelectronic protective devices-out of AUXout of AUXunlimitedASi profile cable1 Single addressReset output for optoelectronic protective devices
BWU23701 x 2 channelsoptoelectronic protective devices-out of AUXout of AUXunlimitedASi via M121 Single address-
BWU29601 x 2 channelsoptoelectronic protective devices-out of ASiout of ASiunlimitedASi via M121 Single address-
BWU28141 x 2 channelscomplementary switch-out of ASiout of AUXmax. 15 mASi profile cable1 Single address-
BW34896-8 x 2 channels; depending on configurationfloating contacts, optoelectronic protective devices, complementary switchup to 2 release circuits, up to 2 x electronic safe outputs; depending on configurationout of ASiout of ASiunlimitedASi profile cabledepending on configuration-
BW34996-8 x 2 channels; depending on configurationfloating contacts, optoelectronic protective devices, complementary switchup to 2 release circuits, up to 2 x electronic safe outputs; depending on configurationout of ASiout of ASiunlimitedASi via M12depending on configuration-
BW34906-8 x 2 channels; depending on configurationfloating contacts, optoelectronic protective devices, complementary switchup to 2 release circuits, up to 2 x electronic safe outputs; depending on configurationout of AUXout of AUXunlimitedASi profile cabledepending on configurationmuting
BWU30642 x 2 channelsfloating contacts, optoelectronic protective devices4 release circuits, 4 x electronic safe outputsout of AUXout of AUXunlimitedASi profile cabledepending on configuration-
BWU43791 x 2 channelsfloating contacts1 release circuit, 2 x relayout of AUX-unlimitedASi profile cable2 Single addresses + 1 AB address-

 

 

Safety I/O Modules: Active Distributors ASi Safety, IP67

Figure Inputs Safety, SIL 3, Cat. 4 Safety signal inputs

inputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

Input voltage (sensor supply)

Electronic outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

Output voltage (actuator supply)

PUR line, oil resistant. Further connection options are available on request.

      M12 socket M12 cable socket, angled  M12 cable socket, straight   M8 cable socket, straight   round cable/connecting wires     profile cable branch          push in terminals
       2 x round cables/connecting wires 2,5 mm²

Connection

Single wiring: 1 input or output per connection.

 

Y wiring: 2 inputs or outputs per connection.

 

Mixed wiring: 1 input and 1 output per connection.

 

Exact pin assignment see data sheet.

M8/M12 wiring

Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled.

In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted.

Round cable

Modules with a flat housing design and with cables which exit the sides make these ideal for installation in cable ducts, cable channels, cable troughs, cable rails or cable trays. Please note the respective housing depth for your particular installation.

Flat design, installation in cable duct possible

status of in- and outputs is indicated by LEDs. In addition to that, both ASi LEDs (PWR green and FAULT red) show - as usual regarding the ASi modules - the status of the ASi modules. Uaux is indicated by a green LED.

LED status display
Profile cable connection

AB address (max. 62 AB addresses/ASi network), 2 AB addresses (max. 31 modules with 2 AB addresses), Single addresses (max. 31 Single addresses/ASi network), ASi-5 address (max. 62 ASi-5 addresses/ASi network), mixed use allowed.
For ASi modules with two ASi nodes the second Asi node is turned off as long as the first Asi node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

ASi address
Special function Article No.
BWU36041 x 2 channelsfloating contactsout of ASiout of ASi1 x round cable/connecting wires + 1 x ASi addressing cable socket-2 myes, depth: 35 mmyes1 x ASi1 Single addressto connect 2 x NC contacts to ASi
BWU34251 x 2 channelsfloating contactsout of ASiout of AUX1 x round cable/connecting wires-1 myes, depth: 35 mmyes1 x ASi, 1 x AUX 24 V1 Single addressto connect 2 x NC contacts to ASi
BWU37501 x 2 channelsfloating contactsout of ASiout of AUX1 x M12 cable socket, straight, 8 poles-1 myes, depth: 35 mmyes1 x ASi, 1 x AUX 24 V1 Single address-
BWU37181 x 2 channelsoptoelectronic protective devicesout of AUXout of AUX1 x M12 cable socket, straight 8 poles + 1 x M12 cable socket, straight, 5 poles-10 myes, depth: 19 mmyes1 x ASi, 1 x AUX 24 V1 Single addressto connect Leuze MLC530SPG (operation mode 5) to ASi
BWU37251 x 2 channelsoptoelectronic protective devicesout of AUXout of AUX1 x M12 cable socket, straight 8 poles + 1 x M12 cable socket, straight, 5 poles-SI/O: 0,5 m, 24V: 2 myes, depth: 19 mmyes1 x ASi, 1 x AUX 24 V1 Single addressTo connect Sick deTec4 to ASi
BWU32491 x 2 channelsfloating contactsout of ASiout of ASi2 x round cables/connecting wires-1 myes, depth: 19 mmyes1 x ASi1 Single addressto connect 2 x NC contacts to ASi
BWU36001 x 2 channelsfloating contactsout of ASi-2 x round cables/connecting wires-10 myes, depth: 19 mmyes1 x ASi1 Single addressto connect 2 x NC contacts to ASi
BWU37191 x 2 channelsoptoelectronic protective devicesout of AUXout of AUX1 x M12 cable socket, straight, 8 poles-2 myes, depth: 19 mmyes1 x ASi, 1 x AUX 24 V1 Single addressto connect Leuze MLD530-RT3M (operation mode 5) to ASi
BWU41661 x 2 channelsoptoelectronic protective devicesout of AUXout of AUX1 x round cable/connecting wires-2 myes, depth: 19 mmyes1 x ASi, 1 x AUX 24 V1 Single addressto connect Leuze MLD530-RT3M to ASi
BWU35991 x 2 channelsfloating contactsout of ASiout of ASi1 x round cable/connecting wires-10 myes, depth: 19 mmyes1 x ASi1 Single addressto connect 2 x NC contacts to ASi
BWU32481 x 2 channelsfloating contactsout of ASiout of ASi1 x round cable/connecting wires-1 myes, depth: 19 mmyes1 x ASi1 Single addressto connect 2 x NC contacts to ASi
BWU33731 x 2 channelsfloating contactsout of ASi-1 x round cable/connecting wires-0,30 myes, depth: 19 mmyes1 x ASi1 Single addressto connect 2 x NC contacts to ASi
BWU35531 x 2 channelsfloating contactsout of ASi-1 x M8 cable socket, straight, 4 poles-0,20 myes, depth: 19 mmyes1 x ASi1 Single addressto connect Sick RE13-SA84 / RE13-SAC / RE23-SAC / RE23-SA84 to ASi
BWU34131 x 2 channelsfloating contactsout of ASi-1 x M12 cable socket, angled, 5 poles-1 myes, depth: 19 mmyes1 x ASi1 Single addressto connect E-STOP buttons to ASi via M12
BWU36261 x 2 channelsfloating contactsout of ASi-1 x M12 cable socket, straight, 5 poles-1 myes, depth: 19 mmyes1 x ASi1 Single addressto connect E-STOP buttons to ASi via M12
BWU37961 x 2 channelsfloating contactsout of ASiout of ASi1 x M12 cable socket, angled, 8 poles-1 myes, depth: 19 mmyes1 x ASi1 Single address-
BWU47021 x 2 channelsfloating contactsout of ASiout of ASi1 x M12 cable socket, straight, 8 poles-1 myes, depth: 19 mmyes1 x ASi1 Single address-
BWU47011 x 2 channelsfloating contactsout of ASi-1 x M12 cable socket, straight, 5 poles-2 myes, depth: 19 mmyes1 x ASi1 Single addressto connect E-STOP buttons to ASi via M12
BW32991 x 2 channelsoptoelectronic protective devicesout of AUXout of AUX1 x M12 cable socket, angled, 5 poles-1 myes, depth: 19 mmyes1 x ASi, 1 x AUX 24 V1 Single address-
BWU36271 x 2 channelsoptoelectronic protective devicesout of AUXout of AUX1 x M12 cable socket, straight, 5 poles-5 myes, depth: 19 mmyes1 x ASi, 1 x AUX 24 V1 Single address-
BWU33761 x 2 channelsoptoelectronic protective devicesout of AUXout of AUX1 x M12 cable socket, straight, 5 poles-1 myes, depth: 19 mmyes1 x ASi, 1 x AUX 24 V1 Single addressto connect Euchner MGB / Pizzato ST GD210MP-G1T to ASi
BWU37211 x 2 channelsoptoelectronic protective devicesout of AUXout of AUX1 x M12 cable socket, straight, 8 poles-5 myes, depth: 19 mmyes1 x ASi, 1 x AUX 24 V1 Single addressto connect Pilz PSENslock, PSENcode to ASi
BWU34881 x 2 channelsoptoelectronic protective devicesout of AUXout of AUX1 x M12 cable socket, straight, 8 poles-1 myes, depth: 19 mmyes1 x ASi, 1 x AUX 24 V1 Single addressto connect Pilz PSENslock, PSENcode to ASi
BWU35651 x 2 channelsoptoelectronic protective devicesout of AUXout of AUX1 x M12 cable socket, straight, 8 poles-1 myes, depth: 19 mmyes1 x ASi, 1 x AUX 24 V1 Single addressto connect Schmersal AZM400 to ASi
BWU36351 x 2 channelsoptoelectronic protective devicesout of AUXout of AUX1 x M12 cable socket, straight, 8 poles-1 myes, depth: 19 mmyes1 x ASi, 1 x AUX 24 V1 Single addressto connect Schmersal AZM200 / AZM201 / AZM300 / MZM100 to ASi

 

 

Safety I/O Modules: Circuit Board Modules ASi, PCB Solutions

  • Special versions on request
Figure Inputs Safety, SIL 3, Cat. 4 Safety signal inputs

inputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

Input voltage (sensor supply)

Electronic outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

Output voltage (actuator supply)
Length of connector cable

Coating protects components and circuit boards when touched.

   thin coated   thick coated
Coating

further connection options are available on request.

screw terminalswiring pins, angled
(pins 180° to PCB)
wiring  pins, straight
(pins 90° to PCB)
solder lugssocketsplug-in spring-type /
screw terminals
   connecting wires
PCB connection

status of in- and outputs is indicated by LEDs. In addition to that, both ASi LEDs (PWR green and FAULT red) show - as usual regarding the ASi modules - the status of the ASi modules. Uaux is indicated by a green LED.

LED status display

The connection to ASi as well to AUX (auxiliary 24 V power) is made via yellow resp. black ASi profile cable with piercing technology or via M12 socket (in IP20 via clamps).


Line protection: If the module is supplied via a M12 connection with A or B coding, it may only be used with a current load of max. 4 A per pin in acc. with IEC 61076-2-101 and IEC 61076-2-109. A fused tap is recommended. There is no such limitation for modules supplied via piercing contacts.

ASi connection

AB address (max. 62 AB addresses/ASi network), 2 AB addresses (max. 31 modules with 2 AB addresses), Single addresses (max. 31 Single addresses/ASi network), ASi-5 address (max. 62 ASi-5 addresses/ASi network), mixed use allowed.
For ASi modules with two ASi nodes the second Asi node is turned off as long as the first Asi node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

ASi address
Special function Article No.
BWR30671 x 2 channelsfloating contactsout of ASiout of ASimax. 15 mthick coatedconnecting wires, 200 mmyesconnecting wires, 200 mm1 Single addressfor mounting in E-STOP housing
BWR24261 x 2 channelsfloating contactsout of ASiout of ASimax. 15 mthick coatedconnecting wires, 100 mmyesconnecting wires, 100 mm1 Single addressfor mounting in E-STOP housing
BWR25211 x 2 channelsfloating contactsout of ASiout of ASimax. 15 mthick coatedconnecting wires, 100 mm + contact pinsyesconnecting wires, 100 mm1 Single addressfor mounting in E-STOP housing
BWR18961 x 2 channelsfloating contactsout of ASiout of AUXmax. 15 mnoplug-in screw terminalsyesplug-in connecting wires1 Single address-
BWR17511 x 2 channelsfloating contactsout of ASiout of AUXmax. 15 mnoscrew terminalsyesscrew terminals1 Single address-
BW2914--out of AUXout of AUXmax. 3 mthick coatedscrew terminalsyesscrew terminals1 Single address + 2 AB addresses-