Product description

Active Distributor ASi Safety, IP67, housing depth 19 mm, 1 x 2 channels safe input (SIL 3, cat. 4) for floating contacts, 1 digital output, input voltage/sensor supply out of ASi, output voltage/actuator supply out of ASi, periphery connection via 2 x round cables/connecting wires, cable length 1 m, flat design, installation in cable duct possible (installation depth ≥ 19 mm), connection for 1 x ASi profile cable, ASi connection via profile cable and piercing technology, 1 single address

Technical data

Type Active distributor ASi Safety
Housing depth: 19 mm
Protection rating

"IP20":
Protected against solid foreign bodies having a diameter of 12.5 mm or larger and against finger contact, not protected against water.


"IP40":

Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water.

"IP54":

Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.


"IP65":
Dust-tight, full protection against contact, protection against spray water (jet) from any angle.

"IP67":

Dust-tight, full protection against contact, protection against temporary immersion.

IP67
Inputs Safety, SIL 3, Cat. 4 1 x 2 channels
Outputs digital 1 x electronic
Safety signal inputs floating contacts
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of ASi
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

out of ASi
Connection

PUR line, oil resistant. Further connection options are available on request.

      M12 socket M12 cable socket, angled  M12 cable socket, straight   M8 cable socket, straight   round cable/connecting wires     profile cable branch          push in terminals
       2 x round cables/connecting wires 2,5 mm²

2 x round cables/connecting wires
Round cable

Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled.

In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted.

1 m
ASi connection

The connection to ASi as well to AUX (auxiliary 24 V power) is made via yellow resp. black ASi profile cable with piercing technology or via M12 socket (in IP20 via clamps).


Line protection: If the module is supplied via a M12 connection with A or B coding, it may only be used with a current load of max. 4 A per pin in acc. with IEC 61076-2-101 and IEC 61076-2-109. A fused tap is recommended. There is no such limitation for modules supplied via piercing contacts.

ASi profile cable
ASi address

AB address (max. 62 AB addresses/ASi network), 2 AB addresses (max. 31 modules with 2 AB addresses), Single addresses (max. 31 Single addresses/ASi network), ASi-5 address (max. 62 ASi-5 addresses/ASi network), mixed use allowed.
For ASi modules with two ASi nodes the second Asi node is turned off as long as the first Asi node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 Single address
Flat design, installation in cable duct possible

Modules with a flat housing design and with cables which exit the sides make these ideal for installation in cable ducts, cable channels, cable troughs, cable rails or cable trays. Please note the respective housing depth for your particular installation.

yes, depth: 19 mm
Special function to connect 2 x NC contacts to ASi

Manuals

    The product has earned the following certifications: