Logo Bihl+Wiedemann GmbH

Circuit Board Modules

BWR3116ASi PCB Module, 73 mm x 37,5 mm

Product description

ASi PCB Module, 73 mm x 37,5 mm, 4 digital inputs, 4 digital outputs, input voltage/sensor supply out of ASi, output voltage/actuator supply out of ASi, max. 180 mA for sensor supply, max. 100 mA per output, periphery connection via sockets, ASi connection via sockets, 1 AB address

Technical data

Type circuit board 73 mm x 37,5 mm
Circuit board dimensions

2 holes for assembly angles.

73 mm x 37,5 mm
Inputs digital 4
Outputs digital 4 x electronic
PCB connection

further connection options are available on request.

screw terminalswiring pins, angled
(pins 180° to PCB)
wiring  pins, straight
(pins 90° to PCB)
solder lugssocketsplug-in spring-type /
screw terminals
   connecting wires
sockets
Coating

Coating protects components and circuit boards when touched.

   thin coated   thick coated
no
LED status display

status of in- and outputs is indicated by LEDs. In addition to that, both ASi LEDs (PWR green and FAULT red) show - as usual regarding the ASi modules - the status of the ASi modules. Uaux is indicated by a green LED.

no
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of ASi
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

out of ASi
ASi connection

The connection to ASi as well to AUX (auxiliary 24 V power) is made via yellow resp. black ASi profile cable with piercing technology or via M12 socket (in IP20 via clamps).


Line protection: If the module is supplied via a M12 connection with A or B coding, it may only be used with a current load of max. 4 A per pin in acc. with IEC 61076-2-101 and IEC 61076-2-109. A fused tap is recommended. There is no such limitation for modules supplied via piercing contacts.

sockets
ASi address

AB address (max. 62 AB addresses/ASi network), 2 AB addresses (max. 31 modules with 2 AB addresses), Single addresses (max. 31 Single addresses/ASi network), ASi-5 address (max. 62 ASi-5 addresses/ASi network), mixed use allowed.
For ASi modules with two ASi nodes the second Asi node is turned off as long as the first Asi node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 AB address

The product has earned the following certifications: