I/O Modules
BWU2728ASi Digital Output Module, IP67, M12, 4O
Product description
ASi Digital Output Module in IP67, with 4 x M12 sockets, 4 digital outputs, Y wiring, output voltage/actuator supply out of AUX, 2A per output, periphery connection via 4 x M12 sockets, 5 poles, ASi connection via profile cable and piercing technology, 1 AB address
The substructure module is not included in the scope of delivery.
Technical data
Type | IP67, 4 x M12 | ||||||||||||||||||||
ASi-5/ASi-3 | ASi-3 compatible | ||||||||||||||||||||
Housing | 4 x M12 | ||||||||||||||||||||
Protection rating
"IP20": "IP40": Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water. "IP54": Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.
Dust-tight, full protection against contact, protection against temporary immersion. | IP67 | ||||||||||||||||||||
Outputs digital | 4 x electronic | ||||||||||||||||||||
M8/M12 wiring
Single wiring: 1 input or output per connection.
Y wiring: 2 inputs or outputs per connection.
Mixed wiring: 1 input and 1 output per connection.
Exact pin assignment see data sheet. | Y | ||||||||||||||||||||
Output voltage (actuator supply)
Electronic outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, outputs shall not be connected to earth or to external potential.
For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet. | out of AUX, 2 A per output | ||||||||||||||||||||
Connection
PUR line, oil resistant. Further connection options are available on request.
| 4 x M12 sockets, 5 poles | ||||||||||||||||||||
ASi connection
The connection to ASi as well to AUX (auxiliary 24 V power) is made via yellow resp. black ASi profile cable with piercing technology or via M12 socket (in IP20 via clamps).
| ASi profile cable | ||||||||||||||||||||
ASi address
AB address (max. 62 AB addresses/ASi network), 2 AB addresses (max. 31 modules with 2 AB addresses), Single addresses (max. 31 Single addresses/ASi network), ASi-5 address (max. 62 ASi-5 addresses/ASi network), mixed use allowed. | 1 AB address |
General information
Commissioning
Manuals
EPLAN Macros
Video Tutorial