BWU3306Passive Distributor AUX, 16A/20A, profile cable branch, depth 19 mm, IP67
Product description
Passive Distributor AUX, 16A/20A, housing depth 19 mm, IP67, connections for 2 x AUX profile cables with wire section up to 2,5 mm² for max. 20 A as profile cable branch, flat design, installation in cable duct possible (installation depth ≥ 19 mm)
16 A with 1,5 mm2 wire section
20 A with 2,5 mm2 wire section
Technical data
Profile cable connection | 2 x AUX, 16 A/20 A | ||||||||||||||||||||
Connection
PUR line, oil resistant. Further connection options are available on request.
| profile cable branch | ||||||||||||||||||||
Internal fuse
"4 A, changeable": The internal protection is realized via changeable 4 A fuses (slow-blow) for ASi and AUX. At each M12 connection ≤4 A are available. "1 A, self-resetting": The internal protection is realized via self-resetting 1 A fuses for ASi and AUX. At each M12 connection ≤1 A are available. "8 A, slow-blow fuse + 1 A, self-resetting": The internal protection is realized via one 8 A slow-blow fuse for AUX and via one self-resetting 1 A fuse for ASi. At each M8 connection (AUX) ≤6 are available, at each M8 connection (ASi) ≤1 A are available. | no | ||||||||||||||||||||
Round cable
Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled. In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted. | no | ||||||||||||||||||||
Flat design, installation in cable duct possible
Modules with a flat housing design and with cables which exit the sides make these ideal for installation in cable ducts, cable channels, cable troughs, cable rails or cable trays. Please note the respective housing depth for your particular installation. | yes, depth: 19 mm | ||||||||||||||||||||
LED status display
status of in- and outputs is indicated by LEDs. In addition to that, both ASi LEDs (PWR green and FAULT red) show - as usual regarding the ASi modules - the status of the ASi modules. Uaux is indicated by a green LED. | no |
General information
Commissioning
Manuals