Safety Monitor
The Safety Monitor enables safe transmission and processing of safety relevant data from safety input modules and safe shut-off of safety output modules remotely over ASi right where the potentially hazardous motion takes place. And always PLe compliant.
Bihl+Wiedemann offers the Safety Monitor for ASi Safety at Work as a stand-alone device for expanding existing ASi circuits with safety modules. For new systems we can provide our ASi-3 resp. ASi-5/ASi-3 gateways with integrated Safety Monitor and interfaces for the most commonly used automation systems using the most efficient method for safely constructing 1 or 2 ASi circuits at the same time. Even large applications with up to 1922 safety I/Os can be implemented with these devices using our “Safe Link over Ethernet” technology by connecting multiple gateways safely over Ethernet/Profinet.
For small applications with three or more safe signals you should consider our Safety Basic Monitor, a compact safety controller without gateway but with configurable status outputs. The module allows for universal expansion and is also ideal as a head station for special safety applications.
Safety Basic Monitors
- Safety controllers, compact safety controller, programmable safety components
Figure |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix backplane POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Safety communication | Inputs Safety, SIL 3, Cat. 4 | Outputs Safety, SIL 3, cat. 4 | ASi-5/ASi-3 | Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | Article No. |
---|---|---|---|---|---|---|---|---|
![]() | ASi monitors | Safe Link | 3 x 2 channels, input 3 optional for speed monitor (up to 4 kHz) | 2 release circuits, 2 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 0,5 A/ASi network, max. 8 A with ASi power supply | BWU2852Safety Basic Monitor with extended features, 1 ASi master |
![]() | ASi monitors | - | 4 x 2 channels, inputs 3+4 optional for speed monitor (up to 4 kHz) | 2 release circuits, 2 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 0,5 A/ASi network, max. 8 A with ASi power supply | BWU2700Safety Basic Monitor with extended features, 1 ASi master |
![]() | ASi monitors | - | 4 x 2 channels, inputs 3+4 optional for speed monitor (up to 4 kHz) | 2 release circuits, 2 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 0,5 A/ASi network, max. 8 A with ASi power supply | BW2512Safety Basic Monitor Starter Kit |
Safety Basic Monitors, compatible as replacement with ASi Consortium Safety Monitor
- Safety controllers, compact safety controller, programmable safety components
- Compatible as replacement with ASi Consortium Safety Monitor
Figure |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix backplane POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Safety communication | Inputs Safety, SIL 3, Cat. 4 | Outputs Safety, SIL 3, cat. 4 | ASi-5/ASi-3 | Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | Article No. |
---|---|---|---|---|---|---|---|---|
![]() | ASi monitors | - | 4 x 2 channels, inputs 3+4, compatible as replacement with consortial monitor | 2 release circuits, 2 x electronic safe outputs | ASi-3 compatible | 1 ASi network, no ASi Master, ASi Monitor | no, max. 8 A/ASi network | BWU2567Safety Basic Monitor with extended features, 1 ASi monitor |
Safety, PROFINET
- Safety diagnostics in real-time
- Cost-optimized solution for medium-size and large systems
Figure |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix backplane POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Safety communication | Inputs Safety, SIL 3, Cat. 4 | Outputs Safety, SIL 3, cat. 4 | ASi-5/ASi-3 | Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | Article No. |
---|---|---|---|---|---|---|---|---|
![]() | PROFINET | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 2 ASi networks, 2 ASi-3 Masters | yes, max. 4 A/ASi network | BWU2828ASi-3 PROFINET Gateway with integrated Safety Monitor, 2 ASi masters |
![]() | PROFINET | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 4 A/ASi network | BWU2798ASi-3 PROFINET Gateway with integrated Safety Monitor, 1 ASi master |
![]() | PROFINET | PROFIsafe (F-CPU) + Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 2 ASi networks, 2 ASi-3 Masters | yes, max. 4 A/ASi network | BWU3367ASi-3 PROFIsafe via PROFINET Gateway with integrated Safety Monitor, 2 ASi masters |
![]() | PROFINET | PROFIsafe (F-CPU) | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 4 A/ASi network | BWU2794ASi-3 PROFIsafe via PROFINET Gateway with integrated Safety Monitor, 1 ASi master |
![]() | PROFINET, OPC UA | PROFIsafe (F-CPU) + Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 2 ASi networks, 2 ASi-5/ASi-3 Masters | yes, max. 4 A/ASi network | BWU3674ASi-5/ASi-3 PROFIsafe via PROFINET Gateway with integrated Safety Monitor, 2 ASi-5/ASi-3 masters |
![]() | PROFINET, OPC UA | PROFIsafe (F-CPU) + Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 1 ASi network, 1 ASi-5/ASi-3 Master | yes, max. 4 A/ASi network | BWU3862ASi-5/ASi-3 PROFIsafe via PROFINET Gateway with integrated Safety Monitor, 1 ASi-5/ASi-3 master |
![]() | PROFINET, OPC UA | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 2 ASi networks, 2 ASi-5/ASi-3 Masters | yes, max. 4 A/ASi network | BWU4000ASi-5/ASi-3 PROFINET Gateway with integrated Safety Monitor, 2 ASi-5/ASi-3 masters |
![]() | PROFINET, OPC UA | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 1 ASi network, 1 ASi-5/ASi-3 Master | yes, max. 4 A/ASi network | BWU3863ASi-5/ASi-3 PROFINET Gateway with integrated Safety Monitor, 1 ASi-5/ASi-3 master |
![]() | PROFINET, OPC UA | PROFIsafe (F-CPU) + Safe Link | - | - | ASi-5 + ASi-3 compatible | 2 ASi networks, 2 ASi-5/ASi-3 Masters | yes, max. 4 A/ASi network | BWU3833ASi-5/ASi-3 PROFIsafe via PROFINET Gateway with integrated Safety Monitor, 2 ASi-5/ASi-3 master |
![]() | PROFINET, OPC UA | PROFIsafe (F-CPU) + Safe Link | - | - | ASi-5 + ASi-3 compatible | 1 ASi network, 1 ASi-5/ASi-3 Master | yes, max. 4 A/ASi network | BWU4018ASi-5/ASi-3 PROFIsafe via PROFINET Gateway with integrated Safety Monitor, 1 ASi-5/ASi-3 master |
![]() | PROFINET, OPC UA | Safe Link | - | - | ASi-5 + ASi-3 compatible | 1 ASi network, 1 ASi-5/ASi-3 Master | yes, max. 4 A/ASi network | BWU3998ASi-5/ASi-3 PROFINET Gateway with integrated Safety Monitor, 1 ASi-5/ASi-3 master |
Safety, EtherNet/IP + ModbusTCP
- Safety diagnostics in real-time
- Cost-optimized solution for medium-size and large systems
Figure |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix backplane POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Safety communication | Inputs Safety, SIL 3, Cat. 4 | Outputs Safety, SIL 3, cat. 4 | ASi-5/ASi-3 | Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | Article No. |
---|---|---|---|---|---|---|---|---|
![]() | EtherNet/IP + ModbusTCP, OPC UA | CIP Safety over EtherNet/IP + Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 2 ASi networks, 2 ASi-3 Masters | yes, max. 4 A/ASi network | BWU3683ASi-3 CIP Safety over EtherNet/IP + ModbusTCP Gateway with integrated Safety Monitor, 2 ASi masters |
![]() | EtherNet/IP + ModbusTCP | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 2 ASi networks, 2 ASi-3 Masters | yes, max. 4 A/ASi network | BWU3543ASi-3 EtherNet/IP + ModbusTCP Gateway with integrated Safety Monitor, 2 ASi masters |
![]() | EtherNet/IP + ModbusTCP | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 2 ASi networks, 2 ASi-3 Masters | no, max. 8 A/ASi network, redundant supply | BWU3544ASi-3 EtherNet/IP + ModbusTCP Gateway with integrated Safety Monitor, 2 ASi masters |
![]() | EtherNet/IP + ModbusTCP | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 4 A/ASi network | BWU3542ASi-3 EtherNet/IP + ModbusTCP Gateway with integrated Safety Monitor, 1 ASi master |
![]() | EtherNet/IP + ModbusTCP, OPC UA | CIP Safety over EtherNet/IP + Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 2 ASi networks, 2 ASi-5/ASi-3 Masters | yes, max. 4 A/ASi network | BWU3857ASi-5/ASi-3 CIP Safety over EtherNet/IP + ModbusTCP Gateway with integrated Safety Monitor, 2 ASi-5/ASi-3 masters |
![]() | EtherNet/IP + ModbusTCP, OPC UA | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 2 ASi networks, 2 ASi-5/ASi-3 Masters | yes, max. 4 A/ASi network | BWU3825ASi-5/ASi-3 EtherNet/IP + ModbusTCP Gateway with integrated Safety Monitor, 2 ASi-5/ASi-3 masters |
![]() | EtherNet/IP + ModbusTCP, OPC UA | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 1 ASi network, 1 ASi-5/ASi-3 Master | yes, max. 4 A/ASi network | BWU3866ASi-5/ASi-3 EtherNet/IP + ModbusTCP Gateway with integrated Safety Monitor, 1 ASi-5/ASi-3 master |
Safety, EtherCAT
- Safety diagnostics in real-time
- Cost-optimized solution for medium-size and large systems
Figure |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix backplane POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Safety communication | Inputs Safety, SIL 3, Cat. 4 | Outputs Safety, SIL 3, cat. 4 | ASi-5/ASi-3 | Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | Article No. |
---|---|---|---|---|---|---|---|---|
![]() | EtherCAT | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 2 ASi networks, 2 ASi-3 Masters | yes, max. 4 A/ASi network | BWU2944ASi-3 EtherCAT Gateway with integrated Safety Monitor, 2 ASi masters |
![]() | EtherCAT | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 4 A/ASi network | BWU2797ASi-3 EtherCAT Gateway with integrated Safety Monitor, 1 ASi master |
![]() | EtherCAT, OPC UA | FSoE + Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 2 ASi networks, 2 ASi-5/ASi-3 Masters | yes, max. 4 A/ASi network | BWU3858ASi-5/ASi-3 Safety over EtherCAT Gateway with integrated Safety Monitor, 2 ASi-5/ASi-3 masters |
![]() | EtherCAT, OPC UA | FSoE + Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 1 ASi network, 1 ASi-5/ASi-3 Master | yes, max. 4 A/ASi network | BWU3583ASi-5/ASi-3 Safety over EtherCAT Gateway with integrated Safety Monitor, 1 ASi-5/ASi-3 master |
![]() | EtherCAT, OPC UA | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 1 ASi network, 1 ASi-5/ASi-3 Master | yes, max. 4 A/ASi network | BWU3991ASi-5/ASi-3 EtherCAT Gateway with integrated Safety Monitor, 1 ASi-5/ASi-3 master |
Safety, POWERLINK
- Safety diagnostics in real-time
- Cost-optimized solution for medium-size and large applications
Figure |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix backplane POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Safety communication | Inputs Safety, SIL 3, Cat. 4 | Outputs Safety, SIL 3, cat. 4 | ASi-5/ASi-3 | Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | Article No. |
---|---|---|---|---|---|---|---|---|
![]() | POWERLINK, OPC UA | openSAFETY over POWERLINK + Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 2 ASi networks, 2 ASi-5/ASi-3 Masters | yes, max. 4 A/ASi network | BWU3865ASi-5/ASi-3 openSAFETY via POWERLINK Gateway with integrated Safety Monitor, 2 ASi-5/ASi-3 masters |
![]() | POWERLINK, OPC UA | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 2 ASi networks, 2 ASi-5/ASi-3 Masters | yes, max. 4 A/ASi network | BWU3828ASi-5/ASi-3 POWERLINK Gateway with integrated Safety Monitor, 2 ASi-5/ASi-3 Master |
![]() | POWERLINK | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 2 ASi networks, 2 ASi-3 Masters | yes, max. 4 A/ASi network | BWU3176ASi-3 POWERLINK Gateway with integrated Safety Monitor, 2 ASi-3 masters |
![]() | POWERLINK | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 4 A/ASi network | BWU3177ASi-3 POWERLINK Gateway with integrated Safety Monitor, 1 ASi-3 master |
Safety, Sercos
- Safety diagnostics in real-time
- Cost-optimized solution for medium-size and large systems
Figure |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix backplane POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Safety communication | Inputs Safety, SIL 3, Cat. 4 | Outputs Safety, SIL 3, cat. 4 | ASi-5/ASi-3 | Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | Article No. |
---|---|---|---|---|---|---|---|---|
![]() | Sercos, OPC UA | safe Schneider drives over Sercos + Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 2 ASi networks, 2 ASi-5/ASi-3 Masters | yes, max. 4 A/ASi network | BWU3861ASi-5/ASi-3 safe Schneider drives over Sercos Gateway with integrated Safety Monitor, 2 ASi-5/ASi-3 masters |
![]() | Sercos, OPC UA | CIP Safety over Sercos + Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-5 + ASi-3 compatible | 2 ASi networks, 2 ASi-5/ASi-3 Masters | yes, max. 4 A/ASi network | BWU3860ASi-5/ASi-3 CIP Safety over Sercos Gateway with integrated Safety Monitor, 2 ASi-5/ASi-3 masters |
![]() | Sercos, OPC UA | CIP Safety over Sercos + Safe Link | - | - | ASi-5 + ASi-3 compatible | 2 ASi networks, 2 ASi-5/ASi-3 Masters | yes, max. 4 A/ASi network | BWU3845ASi-5/ASi-3 CIP Safety over Sercos Gateway with integrated Safety Monitor, 2 ASi-5/ASi-3 masters |
Safety, PROFIBUS
- Safety diagnostics in real-time
- Cost-optimized solution for medium-size and large applications
Figure |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix backplane POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Safety communication | Inputs Safety, SIL 3, Cat. 4 | Outputs Safety, SIL 3, cat. 4 | ASi-5/ASi-3 | Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | Article No. |
---|---|---|---|---|---|---|---|---|
![]() | PROFIBUS | PROFIsafe (F-CPU) | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 4 A/ASi network | BWU2819ASi-3 PROFIsafe via PROFIBUS Gateway with integrated Safety Monitor, 1 ASi-3 master |
![]() | PROFIBUS | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 2 ASi networks, 2 ASi-3 Masters | yes, max. 4 A/ASi network | BWU2822ASi-3 PROFIBUS Gateway with integrated Safety Monitor, 2 ASi-3 masters |
![]() | PROFIBUS | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 4 A/ASi network | BWU2793ASi-3 PROFIBUS Gateway with integrated Safety Monitor, 1 ASi-3 master |
Safety, BACnet/IP
- Safety diagnostics in real-time
- Cost-optimized solution for medium-size and large applications
Figure |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix backplane POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Safety communication | Inputs Safety, SIL 3, Cat. 4 | Outputs Safety, SIL 3, cat. 4 | ASi-5/ASi-3 | Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | Article No. |
---|---|---|---|---|---|---|---|---|
![]() | BACnet/IP, OPC UA | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 2 ASi networks, 2 ASi-3 Masters | yes, max. 8 A/ASi network | BWU4780ASi-3 BACnet/IP Gateway with integrated Safety Monitor, 2 ASi-3 masters |
![]() | BACnet/IP, OPC UA | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 2 ASi networks, 2 ASi-3 Masters | no, max. 8 A/ASi network, redundant supply | BWU4001ASi-3 BACnet/IP Gateway with integrated Safety Monitor, 2 ASi masters |
Safety, DeviceNet
Figure |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix backplane POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Safety communication | Inputs Safety, SIL 3, Cat. 4 | Outputs Safety, SIL 3, cat. 4 | ASi-5/ASi-3 | Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | Article No. |
---|---|---|---|---|---|---|---|---|
![]() | DeviceNet | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 4 A/ASi network | BWU2972ASi-3 DeviceNet Gateway with integrated Safety Monitor, 1 ASi-3 master |
Safety, CANopen
Figure |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix backplane POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Safety communication | Inputs Safety, SIL 3, Cat. 4 | Outputs Safety, SIL 3, cat. 4 | ASi-5/ASi-3 | Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | Article No. |
---|---|---|---|---|---|---|---|---|
![]() | CANopen | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 4 A/ASi network | BWU2804ASi-3 CANopen Gateway with integrated Safety Monitor, 1 ASi-3 master |
Safety, CC-Link
- Safety diagnostics in real-time
- Cost-optimized solution for medium-size and large systems
Figure |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix backplane POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Safety communication | Inputs Safety, SIL 3, Cat. 4 | Outputs Safety, SIL 3, cat. 4 | ASi-5/ASi-3 | Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | Article No. |
---|---|---|---|---|---|---|---|---|
![]() | CC-Link | Safe Link | 3 x 2 channels | 6 release circuits, 6 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 4 A/ASi network | BWU2833ASi-3 CC-Link Gateway with integrated Safety Monitor, 1 ASi-3 master |
Starter Kits
- Fully assembled and wired in a practical case
Figure |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix backplane POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Safety communication | Inputs Safety, SIL 3, Cat. 4 | Outputs Safety, SIL 3, cat. 4 | ASi-5/ASi-3 | Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | Article No. |
---|---|---|---|---|---|---|---|---|
![]() | ASi monitors | - | 4 x 2 channels, inputs 3+4 optional for speed monitor (up to 4 kHz) | 2 release circuits, 2 x electronic safe outputs | ASi-3 compatible | 1 ASi network, 1 ASi-3 Master | yes, max. 0,5 A/ASi network, max. 8 A with ASi power supply | BW2512Safety Basic Monitor Starter Kit |