With the ASi Slaves/IO-Link Masters from Bihl+Wiedemann intelligent IO-Link sensors and actuators can now be easily incorporated into ASi – exactly there, where they are needed. The IO-Link sensors can be easily parametrized using the configuration tool from Bihl+Wiedemann.
In many application scenarios, IO-Link solutions from Bihl+Wiedemann are much more cost-efficient than similar solutions from other providers. An application with Bihl+Wiedemann is already cheaper than comparable PROFINET variants from three 4-port IO-Link masters. Another factor is the finer granularity. Our 1-port IO-Link master allows you to integrate an IO-Link device exactly where you need it. Thanks to cable-piercing technology, it is extremely easy to install our IO-Link master. You can substantially reduce the time required for assembly.
ASi Slaves/IO-Link Masters: IP67, M12
- IO-Link ports class A
- IO-Link ports class B
- IP67, M12: 2 x 2 connectors for profile cable
Figure | Type | Model | Number of IO-Link Ports | Port class A (M12): Pin 4 configurable (IO-Link/DI/DO), additional digital input at pin 2. Compatible with 3 pol IO-Link devices (M8). Configurable terminals: Terminal assignment (C/Q, L+, L-, I) compatible with pin assigment of IO-Link port class A (M12). Connected IO-Link devices with port class B (M12) with a higher current consumption have to be supplied directly via a separate power supply. Compatible with 3 pol IO-Link devices (M8). | Port class B (M12): Pin 4 configurable (IO-Link/DI/DO), additional power supply (galvanically isolated) for IO-Link devices at pins 2 and 5. Compatible with 3 pol IO-Link devices (M8). Configurable terminals: Terminal assignment (C/Q, L+, L-, I) compatible with pin assigment of IO-Link port class A (M12). Connected IO-Link devices with port class B (M12) with a higher current consumption have to be supplied directly via a separate power supply. Compatible with 3 pol IO-Link devices (M8). | IO-Link and additional inputs/outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs can neither be connected to earth nor to external potential. | Connection via M12: For IO-Link ports class B the supply of actuators is provided by an additional (galvanically isolated) power supply by AUX (auxiliary 24 V power) via Pin 2 (P24) and Pin 5 (N24). Connection via clamps: If connected IO-Link slaves with IO-Link ports class B need a higher current consumption, additionally they can be supplied directly via the power supply. | COM1 = 4.8 kBaud COM2 = 38.4 kBaud COM3 = 230.4 kBaud (optional according to Specification V1.0)
An IO-Link device supports only one of the defined data transmission rates. According to Specification V1.1, the IO-Link master supports all data transmission rates and adapts itself automatically to the data transmission rate supported by the device. | IO-Link specification | PUR line, oil resistant. Further connection options are available on request.
| The connection to ASi as well to AUX (auxiliary 24 V power) is made via yellow resp. black ASi profile cable with piercing technology or via M12 socket (in IP20 via clamps).
| AB Slave (max. 62 AB Slaves/ASi network), 2 AB Slaves (max. 31 modules with 2 AB Slaves), Single Slaves (max. 31 Single Slaves/ASi network), ASi-5 Slave (max. 62 ASi-5 Slaves/ASi network), mixed use allowed. | Article No. | ||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
![]() | IP67, 4 x M12, ASi-5 | ASi slave/IO-Link master | 4 | 2 | 2 | out of AUX | out of AUX | COM1 / COM2 / COM3 | V1.1 | 4 x M12 sockets, 5 poles | ASi profile cable | 1 ASi-5 Slave | BWU4067ASi-5 Slave/IO-Link Master with 4 Ports, IP67, M12, 2 IO-Link Ports Class A/2 IO-Link Ports Class B | ||||||||||||||||||||
![]() | IP67, 4 x M12, ASi-5 | ASi slave/IO-Link master | 4 | 2 | 2 | out of AUX | out of AUX | COM1 / COM2 / COM3 | V1.1 | 4 x M12 sockets, 5 poles | ASi via M12 | 1 ASi-5 Slave | BWU3897ASi-5 Slave/IO-Link Master with 4 Ports, IP67, M12, 2 IO-Link ports class A/2 IO-Link ports class B | ||||||||||||||||||||
![]() | IP67, 4 x M12, ASi-5 | ASi slave/IO-Link master | 4 | 4 | - | out of AUX | - | COM1 / COM2 / COM3 | V1.1 | 4 x M12 sockets, 5 poles | ASi profile cable | 1 ASi-5 Slave | BWU3819ASi-5 Slave/IO-Link Master with 4 Ports, IP67, M12, 4 IO-Link ports class A | ||||||||||||||||||||
![]() | IP67, 4 x M12, ASi-5 | ASi slave/IO-Link master | 4 | 4 | - | out of AUX | - | COM1 / COM2 / COM3 | V1.1 | 4 x M12 sockets, 5 poles | ASi via M12 | 1 ASi-5 Slave | BWU3899ASi-5 Slave/IO-Link Master with 4 Ports, IP67, M12, 4 IO-Link ports class A | ||||||||||||||||||||
![]() | Starter Kits | Gateway | 4 | 2 | 2 | out of AUX | out of AUX | COM1 / COM2 / COM3 | V1.1 | 4 x M12 sockets, 5 poles | ASi profile cable | 1 ASi-5 Slave | BW4211Small Starter Kit ASi-5/IO-Link | ||||||||||||||||||||
![]() | Starter Kits | Gateway | 4 | 2 | 2 | out of AUX | out of AUX | COM1 / COM2 / COM3 | V1.1 | 4 x M12 sockets, 5 poles | ASi profile cable | 1 ASi-5 Slave | BW4229Small Starter Kit ASi-5/IO-Link |
ASi Slaves/IO-Link Master: Active Distributors, IP67
- IO-Link ports class A
- IO-Link ports class B
Figure | Type | Model | Number of IO-Link Ports | Port class A (M12): Pin 4 configurable (IO-Link/DI/DO), additional digital input at pin 2. Compatible with 3 pol IO-Link devices (M8). Configurable terminals: Terminal assignment (C/Q, L+, L-, I) compatible with pin assigment of IO-Link port class A (M12). Connected IO-Link devices with port class B (M12) with a higher current consumption have to be supplied directly via a separate power supply. Compatible with 3 pol IO-Link devices (M8). | Port class B (M12): Pin 4 configurable (IO-Link/DI/DO), additional power supply (galvanically isolated) for IO-Link devices at pins 2 and 5. Compatible with 3 pol IO-Link devices (M8). Configurable terminals: Terminal assignment (C/Q, L+, L-, I) compatible with pin assigment of IO-Link port class A (M12). Connected IO-Link devices with port class B (M12) with a higher current consumption have to be supplied directly via a separate power supply. Compatible with 3 pol IO-Link devices (M8). | IO-Link and additional inputs/outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs can neither be connected to earth nor to external potential. | Connection via M12: For IO-Link ports class B the supply of actuators is provided by an additional (galvanically isolated) power supply by AUX (auxiliary 24 V power) via Pin 2 (P24) and Pin 5 (N24). Connection via clamps: If connected IO-Link slaves with IO-Link ports class B need a higher current consumption, additionally they can be supplied directly via the power supply. | PUR line, oil resistant. Further connection options are available on request.
| Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled. In the case of the active distributors (ASi slaves) however only the one ASi profile cable is counted. | COM1 = 4.8 kBaud COM2 = 38.4 kBaud COM3 = 230.4 kBaud (optional according to Specification V1.0)
An IO-Link device supports only one of the defined data transmission rates. According to Specification V1.1, the IO-Link master supports all data transmission rates and adapts itself automatically to the data transmission rate supported by the device. | IO-Link specification | Modules with a flat housing design and with cables which exit the sides make these ideal for installation in cable ducts, cable channels, cable troughs, cable rails or cable trays. Please note the respective housing depth for your particular installation. | Profile cable connection | The connection to ASi as well to AUX (auxiliary 24 V power) is made via yellow resp. black ASi profile cable with piercing technology or via M12 socket (in IP20 via clamps).
| AB Slave (max. 62 AB Slaves/ASi network), 2 AB Slaves (max. 31 modules with 2 AB Slaves), Single Slaves (max. 31 Single Slaves/ASi network), ASi-5 Slave (max. 62 ASi-5 Slaves/ASi network), mixed use allowed. | Article No. | ||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
![]() | Active distributor ASi-5 | ASi slave/IO-Link master | 2 | 1 | 1 | out of AUX | out of AUX | 2 x M12 cable sockets, straight, 5 poles | 1 m | COM1 / COM2 / COM3 | V1.1 | yes, depth: 35 mm | 1 x ASi, 1 x AUX | ASi profile cable | 1 ASi-5 Slave | BWU4077Active Distributor ASi-5/IO-Link Master with 2 Ports, IP67, M12, 1 IO-Link Port Class A/1 IO-Link Port Class B | ||||||||||||||||||||
![]() | Active distributor ASi-5 | ASi slave/IO-Link master | 1 | - | 1 | out of AUX | out of AUX | 1 x M12 cable socket, straight, 5 poles | 1 m | COM1 / COM2 / COM3 | V1.1 | yes, depth: 35 mm | 1 x ASi, 1 x AUX | ASi profile cable | 1 ASi-5 Slave | BWU4088Active Distributor ASi-5/IO-Link Master with 1 Port, IP67, M12, 1 IO-Link Port Class B |
ASi Slaves/IO-Link Masters: IP20, 22,5 mm
- Cost efficient solution in IP20, 22,5 mm
- IO-Link ports class A
- IO-Link ports class B
- If connected IO-Link devices with port class B (M12) require an andditional power supply, they have to be supplied directly via a separate power supply.
Figure | Type | Model | "Control cabinet": "Decentralized control cabinet": without additional patch terminals or the module has an extremely flat design. | Number of IO-Link Ports | Port class A (M12): Pin 4 configurable (IO-Link/DI/DO), additional digital input at pin 2. Compatible with 3 pol IO-Link devices (M8). Configurable terminals: Terminal assignment (C/Q, L+, L-, I) compatible with pin assigment of IO-Link port class A (M12). Connected IO-Link devices with port class B (M12) with a higher current consumption have to be supplied directly via a separate power supply. Compatible with 3 pol IO-Link devices (M8). | Port class B (M12): Pin 4 configurable (IO-Link/DI/DO), additional power supply (galvanically isolated) for IO-Link devices at pins 2 and 5. Compatible with 3 pol IO-Link devices (M8). Configurable terminals: Terminal assignment (C/Q, L+, L-, I) compatible with pin assigment of IO-Link port class A (M12). Connected IO-Link devices with port class B (M12) with a higher current consumption have to be supplied directly via a separate power supply. Compatible with 3 pol IO-Link devices (M8). | IO-Link and additional inputs/outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs can neither be connected to earth nor to external potential. | Connection via M12: For IO-Link ports class B the supply of actuators is provided by an additional (galvanically isolated) power supply by AUX (auxiliary 24 V power) via Pin 2 (P24) and Pin 5 (N24). Connection via clamps: If connected IO-Link slaves with IO-Link ports class B need a higher current consumption, additionally they can be supplied directly via the power supply. | COM1 = 4.8 kBaud COM2 = 38.4 kBaud COM3 = 230.4 kBaud (optional according to Specification V1.0)
An IO-Link device supports only one of the defined data transmission rates. According to Specification V1.1, the IO-Link master supports all data transmission rates and adapts itself automatically to the data transmission rate supported by the device. | IO-Link specification | PUR line, oil resistant. Further connection options are available on request.
| The connection to ASi as well to AUX (auxiliary 24 V power) is made via yellow resp. black ASi profile cable with piercing technology or via M12 socket (in IP20 via clamps).
| AB Slave (max. 62 AB Slaves/ASi network), 2 AB Slaves (max. 31 modules with 2 AB Slaves), Single Slaves (max. 31 Single Slaves/ASi network), ASi-5 Slave (max. 62 ASi-5 Slaves/ASi network), mixed use allowed. | Article No. | ||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
![]() | IP20, 22,5 mm x 114 mm, 6 x COMBICON, ASi-5 | ASi slave/IO-Link master | control cabinet | 4 | configurable terminals | configurable terminals | out of AUX | - | COM1 / COM2 / COM3 | V1.1 | clamps | clamps | 1 ASi-5 Slave | BWU3843ASi-5 Slave/IO-Link Master with 4 Ports, IP20 |